VERIFIED DATA
| Series | SACE New Emax(常用 Emax) |
|---|---|
| Frame | E1(New Emax),框架电流 1600 A |
| Breaking capacity | N 级 · Icu 50 kA(220–690 V AC) |
| Rated current | 400 A(R400 电流整定插头) |
| Poles | 3P |
| Mounting | 固定式(F) |
| Connection | 水平后接线(HR,Rear flat Horizontal) |
| Trip unit | PR121/P-LI(电子式;长延时 + 瞬时保护) |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage Ui | 1000 V |
| Rated impulse withstand Uimp | 12 kV |
| Rated short-time withstand Icw | 50 kA(1 s)/ 36 kA(3 s) |
| Dimensions | 418 × 296 × 302 mm(3P 固定式) |
| Mechanical durability | 25000 次 |
| Electrical durability | 10000 次(Ue ≤ 440 V;690 V 工况按 8000 次核验) |
| Standard | IEC 60947-2 |
| Lifecycle | 已停产 / 受限(ABB 官方 legacy:limited) |